Operating Instructions Fire alarm system EBL512 G3, V1.1.x

Test of alarm devices (H8/S5)

The programmable outputs
collectively activated via this menu (H8/S5), which makes it possible
to test the alarm devices.
The test cannot be started if a fire alarm already is activated in the
system.
One or all control units can be selected. When the test starts, the
alarm devices will sound continuously (steady) for approx. 5 seconds,
be silent for approx. 25 seconds, sound for approx. 5 seconds and so
61
on.
NOTE! Also disabled (and silenced) alarm devices will be tested.
The test will continue for one hour if not stopped via this menu
(H8/S5) or if a fire alarm is activated in the system.
Text in display
S1 Disconnect loop / zone line input
S2 Re-connect loop / zone line input
S3 Acknowledge SERVICE signal
S4 Clear weekly average
S5 Test of alarm devices
S6 Safe shut down of control unit
S7 Activate address in alarm mode
S8 Synchronize the control units
S9 Change code for service / maintenance
S10 Change code for PC-communication
S5 Test alarm devices
Test alarm devices control unit: 00
60
Including Addressable siren 3377 and Addressable sounder base 3379.
61
For the alarm devices 3377 and 3379 the tone with the highest priority
level (and type "alarm device") will be automatically selected.
60
of type "Alarm device" can be
All
135
Comments
Procedure according to
chapter "Access code for
service / maintenance (H5
and H8)", see page 116.
Write control unit number
or press "►", i.e. select
"All".
Press "
" to start the test.