Operating Instructions Fire alarm system EBL512 G3, V1.1.x
Click "Yes" and the control unit will restart. Regarding the
restart, see also chapter "Restart", page 81.
6. LED "Operation" (L5) will be turned on and the other LEDs will
be turned off.
7. Close the "Download" dialog box.
Follow the same procedure in each control unit.

Control Units in a TLON network

All control units connected to a TLON network shall have the same
software version.
For download of new software in each control unit, follow the
procedure described above.
Since some control units do not have contact with some control units
during the downloading, the following faults might be generated:
FAULT: Control unit xx has no contact with control unit xx,
network x
yyyy-mm-dd hh:mm
FAULT: CU xx has wrong information
yyyy-mm-dd hh:mm
The faults have to be acknowledged.
79