Programming (Ssd Download); Check Loop; Single Control Unit - Panasonic MEW01349 Operating Instructions Manual

Fire alarm system
Table of Contents

Advertisement

Panasonic Electric Works Nordic AB
MEW01349
Rev: -
19
19.1
19.2
Operating Instructions Fire alarm system EBL512 G3, V1.1.x

Programming (SSD download)

The PC program WinG3 is used for programming of the site specific
data (SSD) and to download it into the EBL512 G3 control unit(s)
and/or 1728, 1735, 1736, 1826 & 1828 units.
When the units are running, i.e. the power is turned on and the TLON
network is running, the SSD download can take place.
The PC has to be connected to the USB port (type "B") in a control
unit. Start WinG3. Log on to the control unit, access code for level
3B shall be entered via the PC (WinG3).
In WinG3 (menu "Tools" | "Download SSD..."), you select the unit(s)
to which the SSD shall be downloaded.
SSD (i.e. the installation) will be automatically saved after the
download.

Check Loop

In the WinG3 COM loop icon pop-up menu select "Check Loop".
This function can be used after (or before) the download of SSD. The
function is as follows:
The control unit will find all units that are connected on the COM
loop. For all units the address (1-255) and the type of unit will be
reported to WinG3. All differences compared to the WinG3 SSD will
be listed in WinG3 and can be saved and/or printed out.
NOTE!
During this check the COM loop will be disconnected
(disabled) and no alarms or faults can be activated. Disconnected
COM loop is indicated by the LED Fault / Disablements "General
disablements" (L10).

Single Control Unit

Start the downloading from WinG3. A text message will be shown in
the control unit display "Downloading SSD".
When the download is completed the control unit will restart (see
chapter "Restart", page 81.
After the restart another text message will be shown in the display:
FAULT: Restart control unit nn, code 03
YYYY-MM-DD
HH:MM
If the download was not ok another fault will be generated.
37
After SSD download the control unit will restart. A number of faults
might then be generated, e.g. due to not connected units. This will cause
"heavy traffic" on the network, which might affect (delay) the SSD download
to the other units.
75
37
For security reasons the

Advertisement