Operating Instructions Fire alarm system EBL512 G3, V1.1.x

Presentation number

For each fire alarm point / input / zone, a presentation number,
NNN-NN, has to be programmed. The presentation number is shown
in the c.i.e. display and ext. FBP display
activating fire alarm. It is also used to disable / re-enable fire alarm
points / zones and as trigger conditions in control expressions to
activate programmable outputs.
Together with the presentation number, a user definable 40 characters
text message (alarm text) can be displayed (if programmed).
NOTE! Zone numbers 001-999 can be used but not more than 512
alarm points and/or zones can be used per c.i.e.
This is in accordance with the EN54-2 standard.
16
Also in the Alert Annunciation Units and Presentation Units ("Display
Units").
The presentation number (or a user definable 40 characters text message) can
also be shown in the old type of display units connected to the COM loops.
37
16
, to identify the point / zone
01 – 99 = The address within the zone.
00 = Only the zone number will be
displayed, e.g. used for conventional zone
line inputs.