Re-Enable Zone / Address (H2/B5) - Panasonic MEW01349 Operating Instructions Manual

Fire alarm system
Table of Contents

Advertisement

Panasonic Electric Works Nordic AB
MEW01349
25.5
Action
"Menu"
Scroll to menu H2.
"↵ "
Scroll to menu B5.
"↵ "
"↵ "
"↵ "
Rev: -

Re-enable zone / address (H2/B5)

Disabled alarm points, zone / addresses, are listed in menu H4/U1
from which it is also possible to get a print-out.
Alarm point(s) and/or zones disabled via the "Single reset with
automatic disablement ("encapsulation function"), see page Error!
Bookmark not defined., have to be re-enabled via this menu. A zone
will be displayed as ZZZ-00 (i.e. zone number and address 00).
Re-enabling via this menu has higher priority than automatic re-
enabling.
When all zone / addresses have been re-enabled, The LED
Disablements
there are no other disablements in the system.
Text in display
H2 Disable or re-enable
B1 Disable zone
B2 Disable zone / address
B3 Disable output
B4 Re-enable zone
B5 Re-enable zone / address
B6 Re-enable output
B7 Disable / re-enable output type
B8 Disable / re-enable alarm devices
B9 Disable / re-enable routing equipment
B10 De-activate alert annunciation function
B5 Re-enable zone / address
Re-enable zone / address 001-02
zone / address 002-01
zone / address 006-03
zone / address 073-01
Re-enable zone / address 002-01
zone / address 006-03
zone / address 073-01
Operating Instructions Fire alarm system EBL512 G3, V1.1.x
"General disablements" (L10) will be turned OFF, if
96
Fault /
Comments
According to chapter
"Access", see page 85.
If there are no zone /
addresses to re-enable,
menu B5 will be shown
again. The disabled zone /
addresses will be shown in
a list. Use "▼" or "▲" to
select the zone / address
and press "
".
Re-enable another zone /
address or press "ESC".
Scroll to another menu or
press "ESC".