Operating Instructions Fire alarm system EBL512, V2.7.x

Re-enable zone / address (H2/B5)

Disabled alarm points, zone / addresses, are listed in menu H4/U1.
Alarm points and/or zones disabled via the function "Single
encapsulated reset" (see page 52) have to be re-enabled via this menu.
A zone will be displayed as ZZZ-00 (i.e. zone number and address
00).
Alarm points and/or zones disabled when the "New Zealand FB
Silence switch" (outside switch) is turned OFF, have to be re-enabled
via this menu before they can activate a new alarm.
Re-enabling via this menu has higher priority than automatic re-
enabling.
When all alarm points / zones have been re-enabled, The LED
"Disablements" (L8) will be turned OFF, if there are no other
disablements in the system.
Text in display
Disable or re-enable
Disable zone
Re-enable zone / address
Re-enable zone: 000 Address: 00
Re-enable zone / address
ACCEPT? H2
ACCEPT? B1
ACCEPT? B5
ACCEPT?
ACCEPT? B5
102
Comments
According to chapter
"Access", see page 92.
If there are no zone /
addresses to re-enable,
L
menu B5 will be shown
again. L=a list in which
you can scroll. If it's the
correct zone / address to
re-enable, press "A" to
accept. If not, scroll or
write the wanted zone /
address and press "A" to
accept.
If more re-enablements
shall be done, continue like
above. If not, scroll or
press "Return" to menu
H2. Scroll or press
"Return" to log off.