Add A Control Unit In A Tlon Network; Make Two Tlon Networks One; Delete A Control Unit In A Tlon Network - Panasonic EBL512 Operating Instructions Manual

Fire alarm system ebl512
Hide thumbs Also See for EBL512:
Table of Contents

Advertisement

Panasonic Eco Solutions Nordic AB
MEW01457
Rev: -
18.3
18.4
18.5
Operating Instructions Fire alarm system EBL512, V2.7.x

Add a Control Unit in a TLON network

When adding a control unit to a "running" installation you have to
have the same software (S/W) version in all control units. Often the
new control unit has a newer version than the existing control units.
Normally the latest version is the best to use, i.e. the control units in
the "running" installation have to be upgraded.
is possible to download an earlier S/W version in the new control unit.
Both alternatives are described in chapter "New system program
(S/W) version download", page 84.
Open the current project in TLON Manager, add one control unit and
install (download) it according to the separate TLON network
documentation.
Open the SSD for the current system via Win512. Add one control
unit (and the units connected to it) and download the new SSD
according to chapter "Programming (SSD download)", page 81.

Make two TLON networks one.

It is very important that two or more presentation numbers (Zone-
Address) in the systems are not the same. The system properties have
to be the same.
Use one of the systems and add to it the control units etc. from the
74
other system.
If it is known from the beginning that two systems shall be one in the
future, it is possible to give the control units in the system
respectively, the "final" control unit numbers right from the beginning
in order to get the correct technical numbers in the system documents.
NOTE! Two or more presentation numbers (Zone-Address) in the
systems must not be the same.

Delete a Control Unit in a TLON network

Physically disconnect the control unit, which will generate faults in
the other control units. Acknowledge the faults.
72
If the added unit is an EBL512 G3 control unit it has to have the software
EBL512 G3 United version 2.7.x and all EBL512 control units in the
network have to have the software EBL512 version 2.7.x.
73
If you after S/W download get "FAULT:
control unit xx", read the EBL512 settings (menu Tools | EBL512
settings) and download them again. They will then be downloaded with the
same Win512 version as the S/W and the fault will normally be corrected.
74
It is not possible to merge two TLON Networks into one or copy one
system and paste into another system.
79
72
As an alternative, it
73
Configuration

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents