Operating Instructions Fire alarm system EBL512, V2.7.x
Algorithm
Normal sensitivity & Normal detection (15 s)
High sensitivity & Normal detection (15 s)
Low sensitivity & Normal detection (15 s)
Normal sensitivity & Slow detection (35 s)
High sensitivity & Slow detection (35 s)
Low sensitivity & Slow detection (35 s)
Heat algorithm, Class A1
Heat algorithm, Class A2 (S)
Heat algorithm, Class B (S)
Decision algorithm
Default is N-15 and A1 respectively.

Reset of a week average sensor value

If a sensor (analog smoke detector) is replaced without having
generated SERVICE signal, its week average sensor value has to be
set to the default value otherwise the new / clean sensor will inherit
the old sensor's value. It is possible to clear the week average sensor
value for each sensor individually, see chapter "Clear weekly average
(H8/S5)", page 146. See also chapter "Acknowledge SERVICE signal
(H8/S4)", page 145.
NOTE! Authorised service personnel only, must do the reset to
default value. Used incorrectly it can cause nuisance fire alarms.
100
If some other short name is wanted, it can be changed in Win512. Up to
six characters can be used. In the DBI (Danish) convention, up to five
characters.
101
Low sensitivity and/or slow detection (35 s) might not fulfil the EN54-7
specifications.
102
Analog multi detector 3316 only.
116
Short name
100
(nnnnnn)
N-15
H-15
101
L-15
101
N-35
101
H-35
101
L-35
A1
A2
B
102
Dec