Operating Instructions Fire alarm system EBL512, V2.7.x
something is wrong in the downloaded SSD.
FAULT: SSD, AAU xx, CU xx
AAU=1735 / 1736
There is no SSD (Site Specific Data) downloaded to the unit or
something is wrong in the downloaded SSD.
FAULT: SSD, EPU xx, 1587-board x, CU xx
EPU=1728
There is no SSD (Site Specific Data) downloaded to the unit or
something is wrong in the downloaded SSD.
FAULT: SSD, EPU xx, CU xx
EPU=1728
There is no SSD (Site Specific Data) downloaded to the unit or
something is wrong in the downloaded SSD.
FAULT: SSD, FBP xx, 1587-board x, CU xx
FBP=1826 / 1828
There is no SSD (Site Specific Data) downloaded to the unit or
something is wrong in the downloaded SSD.
FAULT: SSD, FBP xx, CU xx
FBP=1826 / 1828
There is no SSD (Site Specific Data) downloaded to the unit or
something is wrong in the downloaded SSD.
FAULT: Supervised output x, CU xx
If the output is programmed for sounders (type 3 = alarm devices), it
is also indicated by LED "Fault / Disablements Alarm devices" (L13)
blinking.
If the output is programmed for fire brigade tx (type 4 = routing
equipment), it is also indicated by LED "Fault / Disablements Fire
brigade tx" (L15) blinking.
x=0 (S0): Short circuit/break on the connected cable/ equipment
and/or blown fuse F5 or F6, on the connection board.