Panasonic EBL512 Operating Instructions Manual page 120

Fire alarm system ebl512
Hide thumbs Also See for EBL512:
Table of Contents

Advertisement

Panasonic Eco Solutions Nordic AB
MEW01457
"Access"
Scroll to menu H4.
"A"
Scroll to menu U5.
"A"
"A"
""
""
"Access"
Enter code for level 3 (4
digits)
""
Rev: -
Operating Instructions Fire alarm system EBL512, V2.7.x
Show sensor values and setting alarm algorithm for the Analog
photo electric detector 3304:
Text in display
Present system status on display and
printer
Disablement
Printout: (1=yes)
Sensor values
Printout: (1=yes)
Enter technical number: 000000
Sensor: 000001
Momentary: XX.X%/m
Sensor: 000001
Perf Factor: X.XX%/m
Sensor: 000001
Current algorithm: N-15
Access code: _
Access code:
****
Change algorithm: (000001 Current N-15)
L-15
L-35
N-15
Change algorithm: (000001 Current N-15)
L-15
L-35
N-15
ACCEPT? H4
Weekly: XX.X%/m
Min: XX.X%/m
Max: XX.X%/m
N-35
H-15
H-35
N-35
H-15
H-35
118
Comments
According to chapter
"Access", see page 92.
U1
To make a printout, press
U5
"1", else press "A" to
accept.
Write the sensor's techn.
number and/or press "A"
to accept.
This is a list in which
you can scroll or use
"" to see the next
information window for
the selected sensor. Press
"Return" to Enter
technical number.
NOTE!
XX.X%/m = XX.X %
obscuration per meter".
Perf Factor: see below
this table.
N-15 = short name, see
separate table, page 115.
Press "Return" to Enter
technical number or
press "Access" to change
the algorithm.
If login was made with
code for level 3, no code
is needed.
The digits are replaced
(****) in the display
"" or "".
Use