Operating Instructions Fire alarm system EBL512, V2.7.x

User definable text messages download

When a fire alarm is activated (e.g. an addressable alarm point), the
presentation number (Zone & Address) will be shown on the first row
in the control units' and the ext. FBPs' display respectively.
second row will be shown a user definable text message (alarm text) if
programmed.
Each alarm point can have a unique text message. When several
alarms are activated (in one or more zones) and only the zone numbers
are shown, each zone can have a unique text message.
Each zone line input can have a unique text message.
The user definable text messages will be printed out when a printer is
available.
See also chapter "Fire alarm", page 41.
Unique user definable text messages for each alarm point and each
zone line input can also be shown in Display units (2235 / 2236)
connected on the COM loops.
All user definable text messages, up to 40 alphanumeric characters
each, are created and downloaded via Win512.
Instructions, chapter "User definable text messages".
(An "older" DOS based PC program NEWTEXT can also be used, see
Planning Instructions, chapter "Display units (addressable)".

Using "old" SSD

Site Specific Data (SSD) created in an earlier Win512 version can be
opened in e.g. the latest Win512 version, edited if required, saved and
downloaded to an EBL512 with the latest version.
80
Also valid for the Ext. Presentation unit 1728 and the Alert Annunciation
units 1735 / 1736.