LED indicator
L7
General fault (yellow)
L8
Disablements (yellow)
L9
Test mode (yellow)
L10
Door open (yellow)
L11
Fault tx activated (yellow)
L12
Service (yellow)
L13
Fault / Disablements
Alarm devices (yellow)
L14
System fault (yellow)
L15
Fault / Disablements
Fire brigade tx (yellow)
L16
Fire brigade tx delay
(yellow)
Operating Instructions Fire alarm system EBL512, V2.7.x
LED indicators on the Control Panel (CP)
Indicating
Fault(s) (i.e. not acknowledged fault(s)) and/or
acknowledged but not corrected fault(s).
Something in the system is disabled / disconnected.
NOTE! Also valid for "Single encapsulated reset"
One or more zones are in "test mode".
A door is open.
One or more not acknowledged faults in the system
and the output Fault tx (routing equipment) is activated
(i.e. this output must not be disabled).
Test of routing equipment in progress (see menu H1).
One or more sensors have reached the service level.
See menu H4/U6.
One or more outputs (type 3 = alarm device) in the
system are disabled.
Blinking: One or more supervised outputs (type 3 =
alarm device) have generated fault(s).
EBL512 is not running (because of S/W / CPU /
memory fault).
Output(s) for fire brigade tx (routing equipment)
is(are) disabled via menu (H8/S1 or H2/B3) or via an
open door.
Blinking: Routing equipment power supply output
or one or more supervised outputs (type 4 = routing
equipment) have generated fault(s).
The alert annunciation function is enabled, i.e. time
channel controlling this function is "on".
15
See also chapter "Door open", page 35.
16
This is also valid when the c.i.e. has no "contact" with a unit with such an
output, e.g. 3377, 3379, 3361, etc.
17
Connection board 1555 terminal block "P1:37-38", fuses F1 and F3.
18
This is also valid when the c.i.e. has no "contact" with a unit with such an
output, e.g. 3361, etc.
19
The Alert Annunciation function is described in the EBL512 Planning
Instructions, chapter "Alert annunciation". The LED "L16" will be "on" if
the AA function is enabled for at least one alarm point / zone. Normally is
only one time channel used for this function but two or more channels can be
used. The AA function can, as an alternative, be continuously "on".
19
15
15
12
.
16
17
18
19