Panasonic EBL512 Operating Instructions Manual page 62

Fire alarm system ebl512
Hide thumbs Also See for EBL512:
Table of Contents

Advertisement

Panasonic Eco Solutions Nordic AB
MEW01457
Rev: -
Operating Instructions Fire alarm system EBL512, V2.7.x
FAULT: Comm. AAU xx, CU xx
AAU=1735 / 1736.
 The contact with the AAU is interrupted. Check the cable,
and all connections. Is correct / complete SSD downloaded
(via Win512)? Check the address setting, SW mode setting,
etc.
 If there is a program memory fault in the AAU, there will be
a fault message in the AAU display:
program area (n)"
FAULT: Comm. EPU xx, 1587-board x, CU xx
EPU=1728.
 The contact with the EPU is interrupted. Check the cable,
all connections and the 1587 board. Is correct / complete
SSD downloaded (via Win512)? Check the address setting
(1587 board / the EPU), SW mode setting, etc.
 If there is a program memory fault in the EPU, there will be
a fault message in the EPU display:
program area (n)"
FAULT: Comm. EPU xx, CU xx
EPU=1728.
 The contact with the EPU is interrupted. Check the cable
and all connections. Is correct / complete SSD downloaded
(via Win512)? Check the address setting, SW mode setting,
etc.
 If there is a program memory fault in the EPU, there will be
a fault message in the EPU display:
program area (n)"
FAULT: Comm. FBP xx, 1587-board x, CU xx
FBP=1826 / 1828.
 The contact with the ext. FBP is interrupted. Check the
cable, all connections and the 1587 board.
complete SSD downloaded (via Win512)?
address setting (1587 board / the ext. FBP), SW mode
setting, etc.
 If there is a program memory fault in the ext. FBP, there will
be a fault message in the ext. FBP display:
fault in program area (n)"
FBP will not work.
60
"Memory fault in
(n=1 or 2). The AAU will not work.
"Memory fault in
(n=1 or 2). The EPU will not work.
"Memory fault in
(n=1 or 2). The EPU will not work.
(n=1 or 2). The ext.
Is correct /
Check the
"Memory

Hide quick links: