Operating Instructions Fire alarm system EBL512, V2.7.x

Test alarm devices (H8/S7)

The programmable outputs
activated via this menu (H8/S7), which make it possible to test the
alarm devices.
The test cannot be started if fire alarm is activated in the system.
One or all control units can be selected. When the test starts the alarm
devices will sound for approx. 5 seconds, be silent for approx. 25
seconds, sound for approx. 5 seconds and so on.
NOTE! Also disabled (and silenced) alarm devices will be tested.
The test will continue for one hour, is stopped via this menu (H8/S7)
or if a fire alarm is activated in the system.
Text in display
Test alarm devices
Test alarm devices on CU 00? (99 = All)
Test of alarm devices in progress.
End test?
Test alarm devices
116
Including Addressable siren 3377 and Addressable sounder base 3378.
117
The output activation will be continuously (steady).
devices 3377 and 3378, the tone with the highest priority level (and type
"alarm device") will be automatically selected.
116
type "Alarm device" can be collectively
ACCEPT?
ACCEPT?
ACCEPT?
ACCEPT?
148
117
Comments
According to chapter
"Access code for
maintenance", see page
141.
S7
Write a CU no. (or "99"
for all CUs) and press "A"
to accept.
The test will continue for
one hour if not stopped via
this menu (S7) or if a fire
alarm is activated in the
system. Press "A" to
accept / stop the test.
Scroll or press "Return" to
S7
return to menu H8. Scroll
or press "Return" to log
off.