15.4.2.1
15.4.3
15.5
15.6
Operating Instructions Fire alarm system EBL512, V2.7.x
Restoring the key after a fire alarm
When all fire alarms (in the system) are reset (see chapter "Alarm
reset", page 51), the key has to be restored in the key cabinet within 5
minutes. If not, a fault will be generated, see chapter "Key cabinet
alarm reset", page 53.

Key cabinet alarm, DBI convention

NOTE! Valid for the DBI (Danish) convention only.
When the key cabinet is opened, the "Fault tx" output(s) will be
activated and a "key cabinet fault" will be generated:
FAULT: Key cabinet, control unit: xx
Date: MM-DD
FEJL: Nøgleskab, central xx
(In Danish: "
When this fault is acknowledged (see chapter "Acknowledge
FAULTS (H6)", page 138), there is a 5 minutes delay before a new
"key cabinet fault" can be generated again.

Alarm Acknowledgement Facility (AAF)

One or more Alarm Acknowledgement Facility Controls
the system.
During the Acknowledgement Period (10-60 sec.) there is an
indication in the c.i.e. display:
AAF zone zz, activated
During the Investigation Period (0-3 min.) there is an indication in the
c.i.e. display:
AAF zone zz, investigation in progress
See EBL512 Planning Instructions chapter "Alarm Acknowledgement
Facility (AAF)" for more information regarding the AAF function.

Quiet alarm

Mostly used on the Australian market only.
One or more smoke detectors, programmed for quiet alarm, e.g. used
for fan control (stop / start depending on the type of fan), have passed
the fire alarm level. No normal fire alarm will be activated.
Quiet alarm is normally used in conjunction with the I/O Matrix board
4582 plus an application board for fan control and an I/O unit 3361 for
fan control.
59
The AAF Control is available on the Australian market only.
49
Time: HH:MM
")
59
are used in