This alarm will also generate a fault message, see chapter "Key
cabinet alarm reset", page 43. It is indicated by LED "Fault" (L8).
NOTE! The "Fault tx" output(s) will not be activated by this fault.

Key cabinet opened in conjunction with a fire alarm

The fire brigade personnel can open the key cabinet if a fire alarm
already is activated in the c.i.e. In this case there will be no key
cabinet alarm or fault generated when the key cabinet is opened.
Restoring the key after a fire alarm
When all fire alarms (in the system) are reset (see chapter "Alarm
reset", page 41), the key has to be restored in the key cabinet within 5
minutes. If not, a fault will be generated, see chapter "Key cabinet
alarm reset", page 43.

Key cabinet alarm, DBI convention

NOTE! Only valid for the DBI (Danish) convention.
When the key cabinet is opened, the "Fault tx" output(s) will be
activated and a "key cabinet fault" will be generated:
FAULT: Key cabinet, control unit: xx
Date: MM-DD
FEJL: Nøgleskab, central xx
(In Danish: "
When this fault is acknowledged (see chapter "Acknowledge
FAULTS (H6)", page 116), there is a 5 minutes delay before a new
"key cabinet fault" can be generated again.
40
Time: HH:MM
")