Operating Instructions Fire alarm system EBL512 V2.3.x

Presentation number

For each fire alarm point / input / zone, a presentation number,
NNN-NN, has to be programmed. The presentation number is shown
in the c.i.e. and ext. FBP display(s)
generating fire alarm. It is also used to disable / re-enable fire alarm
points / zones and in control conditions (expressions) to activate the
programmable outputs.
Together with the presentation number, a user definable, 40
characters, text message can be displayed (if programmed).
NOTE! Zone numbers 001-999 can be used but > 512 alarm points or
zones in one c.i.e. is a violation to the EN54-2 standard.
31
The presentation number (or a user definable, 40 characters, text message)
can also shown in the display units connected to the COM loops.