Disable Control Output (H2/B3) - Panasonic EBL512 Operating Instructions Manual

Fire alarm system ebl512 v2.3.x
Hide thumbs Also See for EBL512:
Table of Contents

Advertisement

Panasonic Electric Works Fire & Security Technology Europe AB
MEW00748
24.3
Action
"Access"
Scroll to menu H2.
"A"
Scroll to menu B3.
"A"
"A"
Depending on the
chosen type, 0, 1, 2, 3
resp. 4, the following
will be shown:
Rev: 1

Disable control output (H2/B3)

Control outputs can be individually disabled. Disabled output will
stay in (or return to) the normal condition for the output respectively.
Disabled outputs are listed in menu H4/U1 from which it is also
possible to get a print-out.
Text in display
Disable or re-enable
Disable zone
Disable control output
Disable output control unit: 00 Type: 0
0=Loopunit 1=S 2=R 3=RE 4=ES
(4=ES not valid in Swedish (SBF) convention)
Disable 00 0000 control output 0
Disable S0
Disable R0
Disable relay board 0 output 0
Disable output for extinguishing system
on 1583 board, CU 00
Operating Instructions Fire alarm system EBL512 V2.3.x
ACCEPT? H2
ACCEPT? B1
ACCEPT? B3
ACCEPT?
ACCEPT?
ACCEPT?
ACCEPT?
ACCEPT?
ACCEPT?
78
Comments
According to chapter
"Access", see page 72.
Write C.U. No. and
press:
"0"=RU4 (2265) or
SU4 (2262 / 2263) or
MIO (3361) or
AOU (3364) or
ASI (3377) or
ASB (3378)
"1"=S0-S3
"2"=R0-R1
"3"=Relay board 1581
"4"=1583 board output
"Extinguishing system".
Press "A" to accept.
Regarding the AOU
(3364) unit's output 2:
The fire door functions
will not be disabled.
Regarding the ASI
(3377) & ASB (3378)
units: Control output
0=high priority
1=medium priority
2=low priority
Write the data.
Press "A" to accept.
LED "Disablements"
(L8) will light up.