Disable Output (H2/B3) - Panasonic MEW01091 Operating Instructions Manual

Fire alarm system
Table of Contents

Advertisement

Panasonic Electric Works Nordic AB
MEW01091
25.3
Action
"Access"
Scroll to menu H2.
"A"
Scroll to menu B3.
"A"
"A"
Depending on the
chosen type, 0, 1, 2 or 3
the following will be
shown:
"A"
Rev: 3

Disable output (H2/B3)

Control outputs,
individually disabled. Disabled output will stay in (or return to) the
normal condition for the output respectively.
Text in display
Disable or re-enable
Disable zone
Disable output
Disable output: Type: 0
0=Loop unit 1=S 2=R0 3=EXPB
Disable technical address 000 output 0
Disable S0
Disable R0
Disable expansion board 0 output 0
Disable output: Type: 0
0=Loop unit 1=S 2=R0 3=EXPB
80
Expansion board (EXPB) 0-7.
Relay output 0-7 (4581) alt. Output 0-2 (4583).
EBL128 Operating Instructions V1.1.x
except outputs of type "alarm
ACCEPT? H2
ACCEPT? B1
ACCEPT? B3
ACCEPT?
ACCEPT?
ACCEPT?
ACCEPT?
ACCEPT?
ACCEPT?
84
device", can be
Comments
According to chapter
"Access", see page 78.
Press:
"0"=MIO (3361) or
ASI (3377) or
ASB (3379) or
AOU (3364)
"1"=C.i.e. output S0-S1
"2"=C.i.e. output R0
"3"=C.i.e. exp. board
output.
Press "A" to accept.
Regarding the ASI
(3377) & ASB (3379)
unit outputs:
0=high priority
1=low priority
Write the data.
Press "A" to accept.
LED "Disablements"
(L8) will light up.
If more disablements
shall be done, continue
like above. If not, press
"Return" to menu B3.
Scroll or press "Return"
to menu H2. Scroll or
press "Return" to log off.