17.1
17.2
17.2.1
17.2.2

Alarm reset

Pre-warning reset

Pre-warning is automatically reset.

Fire alarm reset

In the New Zealand convention fire alarms = normal fire alarms
(ALM), acknowledged alarms (ACK) and isolated alarms (ISO).
NOTE! The detectors having activated the fire alarms shall, after
reset, be inspected, tested and replaced when required.
One of the following alarm reset alternatives is valid. This is selected
via Win128. "Multiple reset" is default.

Multiple reset

All the fire alarms will be reset by pressing "Reset" (P4). (According
to the EN54-2 standard).
NOTE! The push button has to be pressed in for min. 0.5 sec.
When all fire alarms are reset, LEDs "Fire" (L1) and "Alarms
queued" (L2) are turned OFF and the display is empty.
All outputs (for fire alarm) have also been reset, i.e. de-activated.
If a key cabinet is installed, the key (to the building) has to be put
back into the key cabinet within 5 minutes. If not, a fault will be
generated and a fault message will be shown in the display, see
chapter "Key cabinet alarm reset, page 52.

Single encapsulated reset

This function, set in Win128, is a violation to the EN54-2 standard.)
Fire alarm reset
Each fire alarm has to be reset one by one.
Press "Reset" (P4) to reset the fire alarm, shown in the display, on the
first row to the left
NOTE! The push button has to be pressed in for min. 0.5 sec.
Output(s) programmed for this fire alarm will also be reset, i.e. de-
activated.
If more than one fire alarm is activated (i.e. if LED:s "Alarms queued"
(L2) are lit) the next fire alarm in the queue is now shown in the
54
If there is a fault condition (e.g. caused by the fire), a fault message will
now be shown in the display.
55
When "Single encapsulated reset" is used, you can make a "Multiple reset"
by pressing "Reset" (P4) and 0.1 sec. later also press "A" (in the keypad) and
hold them pressed for > 0.5 sec.