Panasonic MEW01091 Operating Instructions Manual page 58

Fire alarm system
Table of Contents

Advertisement

Panasonic Electric Works Nordic AB
MEW01091
Rev: 3
FAULT: Battery, techn address xxx
This is valid for an external power supply (e.g. 3366) connected on the
COM loop.
 Batteries (2 x 12 V) are missing or not correctly connected.
 Battery fuse is blown.
FAULT: Cables mixed COM-loop
The two wires L (SA) and C (SB) have been mixed (alternated). Check
so that the wire connections are correct (according to drawing 128-21).
FAULT: Charging ext. power supply
The fault is to be found in the external power supply equipment. A
fault output is connected to a programmable input in the EBL128
system. Check the input as well.
FAULT: Charging, techn addr xxx
This is valid for an external power supply (e.g. 3366) connected on the
COM loop.
The battery charging function is not working all right. The charger
board (3367) may have to be replaced.
FAULT: Checksum system program
A fault in the EBL128 S/W. This is very serious. Call for service
personnel / engineer immediately.
FAULT: Cut-off SCI n <-> SCI n
This fault is indicating a cut-off (break) on the loop or that the COM
loop voltage is too low at the end of the loop (i.e. < 12 V DC).
SCI n <->SCI n describes between which Short Circuit Isolators
(SCI:s) the cut-off is located.
n = A, B, 0, 1, 2, 3, 4, 5, 6 or 7. A & B is the built-in isolator in the
EBL128 A-direction and B-direction respectively, i.e. if no SCI
(4370) is used the information will always be: SCI A <-> SCI B.
If one SCI (4370 no. 0) is used, the information will be:
SCI A <-> SCI 0 or SCI 0 <-> SCI B
...and so on.
If it is a single break (cut-off) on the loop there will be no other fault
messages.
56
EBL128 Operating Instructions V1.1.x

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ebl128

Table of Contents