Door open

A special key is used to open the EBL128 door to get access to the
front, see chapter "Access levels", page 22. The same type of key is
also used to open the ext. FBP door / the key switch. Door open
indicated by LED "Door open" (L10).

LED "Door open"

Valid for the door in EBL128 or an external FBP connected to
EBL128: Door open in EBL128 is indicated by LED "Door open" in
EBL128. Door open in an ext. FBP is indicated by LED "Door open"
in EBL128.
Outputs for routing equipment (Fire
brigade tx and Fault tx)
In Win128 the following can be programmed:
 Disable by door in the control unit: Door open in EBL128 will
disable the output(s) for routing equipment (Fire brigade and fault
tx).
Disabled outputs for routing equipment are indicated by the LED
"Disablements" (L8) and "Fault / Disablements Fire brigade tx"
(L15) and listed in menu H4/U1.
In the display is shown:
Fire alarm routing disabled
(by open door in CU)

Silence buzzer

In Win128 the following can be programmed:
Silence buzzer by door switch: The buzzer will be turned off
as long as the EBL128 door is open.
(This function is a violation to the EN54-2 standard.)
34
In the ext. FBP 1828: when the key is turned to the "position open /
access".
36
EBL128 Operating Instructions V1.1.x