Restore weekly average to default (H8/S2)

If a sensor (analog smoke detector) is replaced without having
generated SERVICE signal, its week average sensor value has to be
restored and set to a default value. If not, the new / clean sensor will
inherit the old sensor's value. The week average sensor value has to
be restored for each replaced sensor individually. First replace the
sensor then restore the week average sensor value as soon as
possible.
The very first week average sensor value after restoring will be
calculated within one hour. Thereafter a new average sensor value
will be calculated each week.
NOTE!
Authorised service personnel only, must use this menu.
Used incorrectly it can cause nuisance fire alarms from a sensor or no
fire alarm at all.
Text in display
Acknowledge SERVICE signal
Restore weekly average to default
Enter zone-address to restore: 00-00
Restore weekly average to default
EBL128 Operating Instructions V1.1.x
ACCEPT? S1
ACCEPT? S2
ACCEPT?
ACCEPT? S2
120