Annual control

The building occupier is highly recommended, once a year, to do
some tests, beside the monthly tests. To avoid the Fault tx output to
be activated, it can be disabled via menu H2/B9 (or via an open door,
se chapter "Door open", page 36.).
Regarding the fault condition, see chapters "Fault", page 54 and "Fault
messages", page 55.
NOTE! Most faults have a time delay.
EBL128 should be tested as follows:
 Perform monthly test (menu H1).
 Remove the battery fuse "F2" on the main board 4556. The
following fault message is to be shown:
FAULT: Battery not connected CU
 Put back the fuse and acknowledge the fault (Menu H6).
 Check the manual call point glasses. Take required
measures. Use the manual call point alarm test key to
activate some fire alarms.
 Check that the control outputs that should be activated really
are activated according to programmed control expressions?
 Reset the fire alarms.