Panasonic Electric Works Nordic AB
MEW01091
Rev: 3
Two or more analog addressable smoke, heat or multi
detectors.
Any manual call point
Any zone line input
Any programmable input with the trigger condition "General
Fire"
Fire alarm presentation in the EBL128 display
1
2
3
4
5
6
7
8
9
0
1
2
3
A
A: Field for the first alarm point or zone in alarm.
By scrolling each alarm will be shown in this field.
B: Field for the most recent (last) zone in alarm.
C: Field for total number of zones in alarm.
D: Field for alarm text. (User definable.)
Comments to the different fields
The information in the field A:
NNN ZONE-ADDR ZZ-AA
or
NNN ZONE ZZ
NNN = a serial number for the displayed alarm, i.e. 001 for the first
activated alarm (ZZ-AA), 002 for the second alarm and so on.
ZZ = zone number 01 – 32. AA = address 01 – 99
The information in the field B:
LAST ZONE zz
zz = zone number 01 – 32 for the most recent zone in alarm.
Displayed also if only one alarm point is in alarm.
The information in the field C:
No. nn
nn = 01 – 32 = the total number of zones (not alarm points) in alarm.
The information in the field D:
A user definable alarm text (max. 40 characters) for the alarm
displayed in the field "A".
42
In the German (VdS) convention and the New Zealand convention the
presentation is different and described in separate documents.
40
EBL128 Operating Instructions V1.1.x