Key Cabinet Alarm; Key Cabinet Opened Before A Fire Alarm - Panasonic MEW01091 Operating Instructions Manual

Fire alarm system
Table of Contents

Advertisement

Panasonic Electric Works Nordic AB
MEW01091
Rev: 3
16.4
16.4.1
 If an ext. FBP with a built-in printer (1826) is connected, the
printer will print
*** Heavy smoke ***
ZONE-ADDR: 12-45
Alarm text for 12-45
or
*** Heavy smoke ***
ZONE: 14
Alarm text for zone 12
*** Heavy heat ***
ZONE-ADDR: 12-45
Alarm text for 12-45
or
*** Heavy heat ***
ZONE: 14
Alarm text for zone 14
Heavy smoke / heat alarm will be reset when the fire alarm
respectively is reset, see chapter "Alarm reset", page 50.

Key cabinet alarm

One programmable input
The fire brigade uses a key cabinet to store a key to the building.
NOTE! In the Danish (DBI) convention the key cabinet alarm
function is a little different, see below.

Key cabinet opened before a fire alarm

If the key cabinet is opened before a fire alarm (e.g. if somebody
illegally breaks into the key cabinet), a key cabinet alarm, i.e. a "fire
alarm" will be generated.
Example; Key cabinet alarm:
ZONE: KE
Alarm from key cabinet
It will be printed like a normal fire alarm if an ext. FBP with printer is
available, see chapter "Fire alarm", page 39.
Key cabinet alarm is reset like a normal fire alarm, see chapter "Fire
alarm reset, page 50.
This alarm will also generate a fault message, see chapter "Key
cabinet alarm reset", page 52. It is indicated by LED "Fault" (L8).
NOTE! The "Fault tx" output will not be activated by this fault.
51
The alarms will be printed like they are presented in the display, i.e. as
ZONE-ADDR or ZONE.
52
Input I0 or COM loop I/O unit 3361 can be used.
47
EBL128 Operating Instructions V1.1.x
51
each heavy smoke / heat alarm, e.g.:
Time HH.MM
Time HH.MM
Date MM-DD
Time HH.MM
Time HH.MM
Date MM-DD
52
can be used to connect a key cabinet.