Key Cabinet Alarm; Co-Incidence Alarm (2-Address / -Zone Dependence) - Panasonic Brooks FireTracker FT1020G3 Operation Manual

Hide thumbs Also See for Brooks FireTracker FT1020G3:
Table of Contents

Advertisement

Fire alarm: 010-01
Menu
Note: The "Ackn. alert annunciation" text is only visible if an AA alarm is activated.
15.5

Key Cabinet Alarm

In some European conventions, the fire brigade personnel use a key cabinet to store a key
for the building. This feature is not used in AU or NZ conventions.
15.6

Co-Incidence Alarm (2-Address / -Zone Dependence)

The co-incidence alarm function is programmed via EBLWin for specific alarm points /
zones.
When only one zone or one zone / address (alarm point) is in alarm state, the FDCIE
buzzer sounds (0.8 / 5 sec.) and there is a Co-incidence alarm presentation in the display.
Note: LEDs "Fire" (L1) are not indicating a co-incidence alarm.
The co-incidence alarm will be automatically Reset after 5 minutes or via the "Reset" button
(P3). See chapter "Alarm reset", page 68.
Example; Co-incidence alarm zone 123, address 45 (within zone 123):
Menu
If more than one Co-incidence alarm not dependent on each other are activated, the LEDs
"SEVERAL ALARMS" (L6) are blinking and the Co-incidence alarms will be automatically
scrolled (each 5
If two or more zones or alarm points (zone / addresses) dependent on each other are in
alarm status at the same time, normal fire alarm (see above) will be activated in the system.
The co-incidence alarm function can be turned on / off via a time channel.
Alert annunciation
010-01
Address
Zone
User definable alarm text for 010-01
CO-incidence alarm
Zone
Address
123-45
User definable alarm text for 123-45
second).
th
Alarm number 1 (of 1)
SMOKE
1 zone in alarm
Ackn. Alert
annunciation
SMOKE
62
Operation Manual
FT1020G3 Rev 2.10.4