Synchronise The Control Units (H8/S7) - Panasonic Brooks FireTracker FT1020G3 Operation Manual

Hide thumbs Also See for Brooks FireTracker FT1020G3:
Table of Contents

Advertisement

29.7

Synchronise the Control Units (H8/S7)

After any Control Unit restart in a network system, synchronisation will start automatically.
Synchronisation can also be started via EBLWin and this menu (H8/S7).
The Control Units must be synchronised when the following fault message is shown:
During the synchronisation, the following information will be displayed in all Control Units
↻ (rotating clockwise) = Synchronisation in progress for the Control Unit (CU).
in the system:
√ = Synchronisation completed successfully for the Control Unit (CU).
<Blank> = Synchronisation failed for the Control Unit (CU).
Action
"Menu"
Scroll to menu H8.
"↲"
Scroll to menu S7.
"↲"
"▼"
"↲"
After a while.
FAULT: Control unit xx has wrong information
Text in display
H8 Maintenance
S1 Dis- / Re-connect loop / zone line input
S2 Acknowledge SERVICE signal
S3 Clear weekly average
S4 Test of alarm devices
S5 Safe shut down of control unit
S6 Activate address in alarm mode
S7 Synchronize the control units
S8 Activate / Reset outputs
S7 Synchronize the control units
Start synchronization?
Synchronisation in progress...
CU00 ↻
CU10 ↻
CU01 ↻
CU11 ↻
CU02 ↻
CU12 ↻
CU03 ↻
CU13 ↻
CU04 ↻
CU14 ↻
CU05 ↻
CU06 ↻
CU17 ↻
CU07 ↻
CU18 ↻
CU08 ↻
CU19 ↻
CU09 ↻
Synchronisation completed
dd-mm-yyyy hh:mm
No
Yes
CU20 ↻
CU21 ↻
CU22 ↻
CU23 ↻
CU24 ↻
CU25 ↻
CU26 ↻
CU27 ↻
CU28 ↻
CU29 ↻
160
Operation Manual
FT1020G3 Rev 2.10.4
Comments
According to chapter
"Access", see page 42.
Press "▼", to select
"Yes". Press "↲" to start
the synchronisation.
During the
synchronisation, the
progress symbol for
each control unit is
shown.
In the example shown,
CU15 & CU16 are not
programmed.