A fan reset switch is provided to independently restore the fan status to the non-alarm
condition as required by AS1670.1:2015 section 7 i.e. reset the alarm in the FDCIE will not
restore the fans to the non-fire condition until the reset switch is pressed.
Two new features are added in the new 19" rack version:
1. Added a fan phase fault LED for each fan to indicate a phase failure in one of the
phases suppling power to the fan. The Phase fail fault indicator conforms to the
requirements of AS1670.1:2015 clause 7.15.6. Same LED exists in the damper
module to indicate power loss to the damper.
2. A common fire mode indicator is added to each module to indicate general fire
alarm.
A remotely located (mechanical services) 4461 module is required for each fan/damper
and configured in the control panel using control type "Fire Ventilation" in EBLWin.
For standard fan configuration e.g. smoke exhaust fans, the standard mode can be used
to program 4461, only one relay required to start / stop the fan whilst for more configuration
options e.g. supply air fans, the enhanced mode is used to provide separate relays to start
and stop the fan.
Controls and indicators of the fan module are explained in EBLWin "Help" and drawings
shown in Figure 24 page 176.
Note: label of damper control module is different to indicate damper status and controls
and configured separately on the EBLWin.

Table 13 Fan indicators and controls

LED indicator & buttons
FIRE MODE General fire mode - Red
RUN
Fan running - Red
STOP
Fan stopped - Green
FAULT
Fan fault - Yellow
Ǿ FLT
Phase fault - Yellow
LED – Red
ON
Button
LED – Green
AUTO
Button
LED - Yellow
OFF
Button
Indicating
Illuminates to indicate general fire.
Illuminates to indicate fan running.
Illuminates when the fan is stopped.
Illuminates when the signal to change the fan status is
restored, either via manual override switch or by the
FDCIE in Auto mode but the feedback signal
confirming the change of state has not been received
by 4461 input connected to the fan pressure switch or
CT within 30 seconds OR:
There is an open circuit in the 4461 supervised input
where the feedback from the pressure switch is
connected OR
The pressure switch is faulty
Illuminates in case of fan power phase failure
Indicates manual start when the "On" button is pressed
Manual override control to start up the fan
manually irrespective of any alarm condition
in the FDCIE.
Indicates "Auto" position of the button, normal operation
Pressed to put the fan in "Auto" mode i.e. the fan may
run or stop automatically depending on the alarm
condition in the FDCIE
Indicates "Off" position of the button, fan stops
manually
Manual override control to stop the fan if it is running
irrespective of any alarm condition in FDCIE.
36