"ESC"
Note: The sensor values for disabled analogue smoke detectors in NORMAL mode will not
be used for calculation of the week average sensor value, i.e. only the values saved before
and after the disablement will be used for this calculation.
Disable --------------------------------------------------------------
Zone _ _ _ address _ _
Automatic re-enable:
Re-enable list
(1)
Zone 003 address 01 autom. re-enable at 17:05
Disable
Zone 000 address 00
Automatic re-enable:
B1 Zone or Zone/Address
B2 Output
B3 Output type
B4 Alarm devices
B5 Routing equipment
B6 Alert annunciation function
Escape
menu
No
Change type
of disablement
No
Change type
of disablement
114
Operation Manual
FT1020G3 Rev 2.10.4
Select in the Re-enable
list "▼" (in this example
there is only one item)
and press "↲".
Re-enabled zone or
zone / address will
disappear from the list,
indicated with a beep.
Disable (or Re-enable)
another Zone, Zone /
Address or press "ESC".
Scroll to another menu
or press "ESC" or
"Escape menu".