Panasonic Brooks FireTracker FT1020G3 Operation Manual page 149

Hide thumbs Also See for Brooks FireTracker FT1020G3:
Table of Contents

Advertisement

The zone(s) will stay in test mode until the test mode is terminated. The test mode is terminated in this
menu or automatically after one hour.
You will be automatically logged out 15 minutes after the latest "action" (using of any key) but the zone(s) will
stay in test mode until the test mode is terminated, see above.
Perform the test as quickly as possible, since the output(s) for routing equipment (fire brigade tx) are disabled
(also the parts of the zones in test mode, not visible for the test personnel, are disabled).
In order to shorten the testing time, any time delay for the detectors / zones in test mode will be "disabled",
i.e. fire alarm will be detected faster than normal.
In the tested alarm point, the LED will light up, and the LEDs "Fire" (L1) in the FDCIE will light up for approx.
10 seconds, then the alarm point will be automatically reset.
An alarm point in test mode will not be able to generate a fault. An alarm point "in alarm" when the test mode
is terminated will activate a normal fire alarm.
"
" for each zone to
end the test mode.
"
"
ESC
Note 1: During the test, the following information will be shown in all other FDCIE displays:
Zone 001 in test mode
Zone 002 in test mode Etc.
Note 2: If an alarm point (e.g. a manual call point) is in alarm state when the test mode is
terminated, a fire alarm will be activated.
Note 3: When the "Fire door closing" function is used, the fire door will be closed when the
detectors controlling the door are tested in test mode.
Set in test mode
Zone 000
H7 Perform ZONE TEST
149
Operation Manual
FT1020G3 Rev 2.10.4
No zones in test mode.
Set new zones in test
mode or press "ESC".
The LED "Test mode"
(L8) is turned OFF.
If more zones are to be
tested, continue as
above. If not, scroll to
another menu or press
"ESC".