Output Type (H2/B3) - Panasonic Brooks FireTracker FT1020G3 Operation Manual

Hide thumbs Also See for Brooks FireTracker FT1020G3:
Table of Contents

Advertisement

23.3

Output Type (H2/B3)

Outputs of the same type can be collectively disabled via menu H2/B3 in a selected Control
Unit or in all Control Units.
Disabled output will stay in (or return to) the normal condition for the output respectively.
Disabled outputs are listed in menu H4/U1.
Action
"Menu"
Scroll to menu H2.
"↲"
Scroll to menu B3.
"↲"
"↲"
Text in display
H2 Disable or re-enable
B1 Zone or Zone/Address
B2 Output
B3 Output type
B4 Alarm devices
B5 Routing equipment
B6 Alert annunciation function
Escape
menu
B3 Output type
Disable output
type
Control outputs in Control unit 00
Disable output type
Control outputs in Control unit 00
-- Re-enable list (1) ---------------------------------------------
All control outputs
All
Change type of
disablements
All
Change type of
disablements
117
Operation Manual
FT1020G3 Rev 2.10.4
Comments
According to chapter
"Access", see page 42.
Via menu B3, outputs of
the same type can be
collectively disabled in
selected control unit or
all.
Use the soft key
"Change type of
disablements" to toggle
between:
Control
Ventilation
Extinguishing
Interlocking
Write control unit no.
when required. Press
"↲" to disable which will
be indicated with "√"
and a beep. The "type"
will be automatically
shown in the Re-enable
list
Use the soft key "|" to
toggle between Disable
and Re-enable list.