Activate Address In Alarm Mode (H8/S6) - Panasonic Brooks FireTracker FT1020G3 Operation Manual

Hide thumbs Also See for Brooks FireTracker FT1020G3:
Table of Contents

Advertisement

29.6

Activate Address in Alarm Mode (H8/S6)

One alarm point (zone-address), not a whole zone, can be set in alarm. It will be presented
in this Control Unit as a fire alarm, the built-in LED in the alarm point e.g. a detector, will be
turned on.
Note: All outputs, standard and programmable, which would have been activated by a real
fire alarm from the same alarm point, will now be activated.
Action
"Menu"
Scroll to menu H8.
"↲"
Scroll to menu S6.
"↲"
Write the zone number
and address (e.g. 123-
45).
"↲"
"↲"
"Reset"
"ESC"
Text in display
H8 Maintenance
S1 Dis- / Re-connect loop / zone line input
S2 Acknowledge SERVICE signal
S3 Clear weekly average
S4 Test of alarm devices
S5 Safe shut down of control unit
S6 Activate address in alarm mode
S7 Synchronize the control units
S8 Activate / Reset outputs
S6 Activate address in alarm mode
(press ↵)
Select zone: 000 address: 00
(press ↵)
Select zone: 123 address: 45
First alarm: 123-45
zone in alarm
Latest alarm: 123-45
-------------------------------------------------------------------------
-----------------
(press ↵)
Select zone: 123 address: 45
S6 Activate address in alarm mode
First alarm: 123-45
Test mode
Zone
123-45
Alarm text for 123-45
Menu
Alarm number 1(of 1)
Address
SMOKE
158
Operation Manual
FT1020G3 Rev 2.10.4
Comments
According to chapter
"Access", see page 42.
1
Press "ESC" to exit this
menu.
The fire alarm has to be
reset as a normal fire
alarm (press "Reset").
Scroll to another menu
or press "ESC".
This manually activated
fire alarm will be
presented as Test mode
alarm" in all control units
and indicated by the
LEDs "Fire" (L1) and
"Fire brigade tx" (L4).
This manually activated
fire alarm must be reset
by the push button
"Reset" (P3)