Activate Address In Alarm Mode (H8/S5) - Panasonic MEW01091 Operating Instructions Manual

Fire alarm system
Table of Contents

Advertisement

Panasonic Electric Works Nordic AB
MEW01091
31.6
Action
"Access"
Scroll to menu S5.
"A"
Write the zone and
address.
"A"
"Return"
Write the zone and
address.
"A"
"Alarms queued"
Rev: 3

Activate address in alarm mode (H8/S5)

One alarm point (zone-address), not a whole zone, can be manually
activated, i.e. be set in alarm status.
NOTE! All outputs, standard and programmable, which would have
been activated by a real fire alarm from the same alarm point, will be
activated by this "manually activated" alarm as well.
Text in display
Acknowledge SERVICE signal
Activate address in alarm mode
Select zone: 00
Select zone: 12
001 ZONE-ADDR 12-45 LAST ZONE 12
"Alarm text for 12-45"
Select zone: 00
Select zone: 12
001 ZONE-ADDR 12-45 LAST ZONE 12
"Alarm text for 12-45"
002 ZONE-ADDR 12-34 LAST ZONE 12
"Alarm text for 12-34"
EBL128 Operating Instructions V1.1.x
ACCEPT? S1
ACCEPT?
address: 00
ACCEPT?
address: 45
ACCEPT?
No. 01
address: 00
ACCEPT?
address: 34
ACCEPT?
No. 01
No. 01
123
Comments
According to chapter
"Access code for service
and maintenance", see
page 118.
S5
Press "A" to accept /
activate the fire alarm.
Normal fire alarm
presentation in the
EBL128 / FBP display.
If more alarm points have
to be set in alarm status,
press "Return" to select
another zone - address and
continue as above.
Press "A" to accept / start
the fire alarm.
The LED:s "Alarms
queued" (L2) are
indicating that more than
one alarm point is in
alarm. Press the button
"Alarms queued" (P1) to
see the other alarm

Advertisement