Re-Enable All Control, Extinguishing, Ventilation Or Alarm Device Outputs (H2/B8) - Panasonic MEW01091 Operating Instructions Manual

Fire alarm system
Table of Contents

Advertisement

Panasonic Electric Works Nordic AB
MEW01091
25.8
Action
"Access"
Scroll to menu H2.
"A"
Scroll to menu B8.
"A"
Press 0, 1, 2 or 3
"A"
"Return"
Rev: 3
Re-enable all control, extinguishing, venti-
lation or alarm device outputs (H2/B8)
Disabled outputs are listed in menu H4/U1.
When all outputs have been re-enabled, the LED "Disablements" (L8)
will be turned OFF, if there are no other disablements.
When all outputs type Alarm devices have been re-enabled, the LED
"Fault / Disablements Alarm devices" (L13) will be turned OFF.
Text in display
Disable or re-enable
Disable zone
Re-enable all control,
or alarm device outputs
Re-enable
type:0 0=Control 1=Ventilation
1=Exting
3=Alarm devices
Re-enable all control,
or alarm device outputs
Disable or re-enable
EBL128 Operating Instructions V1.1.x
ACCEPT? H2
ACCEPT? B1
ventil, exting
ACCEPT? B8
ACCEPT?
ventil, exting
ACCEPT? B8
ACCEPT? H2
90
Comments
According to chapter
"Access", see page 78.
Press:
"0"=control output
"1"=extinguishing output
"2"=ventilation output
"3"=alarm devise output.
Press "A" to accept. LED
"Disablements" (L8) will
turned off.
If type 3 = alarm devices
are re-enabled also the
LED "Fault /
Disablements Alarm
devices" (L13) will be
turned off.
Scroll or press "Return" to
menu H2. Scroll or press
"Return" to log off.