Panasonic Electric Works Nordic AB
MEW01091
25.8
Action
"Access"
Scroll to menu H2.
"A"
Scroll to menu B8.
"A"
Press 0, 1, 2 or 3
"A"
"Return"
Rev: 3
Re-enable all control, extinguishing, venti-
lation or alarm device outputs (H2/B8)
Disabled outputs are listed in menu H4/U1.
When all outputs have been re-enabled, the LED "Disablements" (L8)
will be turned OFF, if there are no other disablements.
When all outputs type Alarm devices have been re-enabled, the LED
"Fault / Disablements Alarm devices" (L13) will be turned OFF.
Text in display
Disable or re-enable
Disable zone
Re-enable all control,
or alarm device outputs
Re-enable
type:0 0=Control 1=Ventilation
1=Exting
3=Alarm devices
Re-enable all control,
or alarm device outputs
Disable or re-enable
EBL128 Operating Instructions V1.1.x
ACCEPT? H2
ACCEPT? B1
ventil, exting
ACCEPT? B8
ACCEPT?
ventil, exting
ACCEPT? B8
ACCEPT? H2
90
Comments
According to chapter
"Access", see page 78.
Press:
"0"=control output
"1"=extinguishing output
"2"=ventilation output
"3"=alarm devise output.
Press "A" to accept. LED
"Disablements" (L8) will
turned off.
If type 3 = alarm devices
are re-enabled also the
LED "Fault /
Disablements Alarm
devices" (L13) will be
turned off.
Scroll or press "Return" to
menu H2. Scroll or press
"Return" to log off.