Re-Enable All Control, Ventilation, Exting Or Interlocking Outputs (B8) - Panasonic EBL128 User Manual

Fire alarm system
Hide thumbs Also See for EBL128:
Table of Contents

Advertisement

Panasonic Eco Solutions Nordic AB
MEW01624 Rev: -
5.8
Re-enable all control, ventilation, exting or
interlocking outputs (B8)
Not available for users with access level / type "Information only".
Disabled outputs are listed in menu H4/U1.
If there is nothing to re-enable, --- List is empty --- will be
shown.
Log in with a User name and Password for typ Building officer (or
Service personnel), see page 5.
H1 Perform monthly test
Scroll (or press "2") to menu H2.
H2 Disable or re-enable
Press "A" to sub menu B1.
B1 Disable zone
Scroll (or press "8") to menu B8.
B8 Re-enable all control, ventilation, exting
or interlocking outputs
Press "A".
Only disabled output types will be shown. Use the keypad to select
output type:
0=Outputs type Control (not control neutral).
1=Outputs type Ventilation
2=Outputs type Extinguishing
3=Output type Interlocking.
Press "A".
When required, re-enable more outputs or press "Return" (P9) until
menu B8 is shown.
Scroll to another menu or press "Return" to menu H2. Scroll to
another menu or leave the menu system by pressing "Return".
EBL128 version 2.0.x, Daily user's manual