Perform ZONE TEST (H7)

Not available for users with access level / type "Information only".
Normally, zones are tested during the monthly test via menu H1. Via
menu H7 it is possible to solely perform the zone test. Up to 99 zones
can be set in test mode, which is indicated by the LED "Test mode"
(L9). In test mode, only the alarm points are tested, i.e. no outputs (no
sounders) will be activated during the test, except the fire door
outputs.
Each test mode alarm will be automatically reset after
approx. 10 seconds.
If a real fire alarm is activated by an alarm point not in test mode,
the normal fire alarm functions will be activated, i.e. fire alarm
presentation, outputs (sounders) activated, routing equipment (fire
brigade tx) activated, etc. but the zone(s) in test mode will remain in
test mode until the test mode is ended.
There will be an automatic ending of the test mode one hour after the
latest tested alarm point / zone.
NOTE! If the door in EBL128 is left open, the output(s) for routing
equipment (fire brigade tx) might be disabled (if set so in EBLWin).
Log in with a User name and Password for typ Building officer (or
Service personnel), see page 5.
H1 Perform monthly test
Scroll (or press "7") to menu H7.
H7 Perform ZONE TEST
Press "A". The sub menu "Set zone in test mode D1" opens.
Press "A". Use the keypad to set one zone (ZZ=01-99) in test mode.
Press "A". The zone ZZ is now in test mode.
Press "A". If more zones shall be set in testmode, do like above, if
not press "Return" to menu D1.
Perform the testing. To end the test mode for one zone press "↓".
The sub menu "End zone in test mode D2" opens.
Press "A". L=This is a list in which you can scroll. Select the zone
for wich the test mode shall be ended.
Press "A". The next zone in the list will be shown. End the test
mode like above. After the last zone
shown.
Press "Return" to menu D2.

Press "Return" to menu H7. Scroll to another menu or leave the
menu system by pressing "Return".
EBL128 version 2.0.x, Daily user's manual
--- List is empty ---