33. PERFORM ZONE TEST (TEST MODE) (H7)

Normally, zones are tested during the monthly test via menu H1. Via this menu (H7) it is also possible to perform the zone test. Up
to 100 zones can be set in test mode.
In test mode, only the alarm points are tested.
No outputs (sounders) will be activated during the test. (Alarm devices can be tested via menu H8/S4 and any output via menu H8/
S8 or via EBLWin when you are logged on.)
If a real fire alarm is activated by an alarm point not in test mode, the normal fire alarm functions will be activated, which means
fire alarm presentation, outputs activated, routing equipment activated, and so on. See also section
on page 18.
ORDER
The Base station must be set back to the "Normal state" for the wireless detectors to function normally.
One or more zones in test mode are indicated by the LED "Test mode" (L8). The green polling LED in the 440x detectors will be
turned off in test mode.
The zones are set one by one in test mode and the test mode has to be ended for each zone one by one.
a) Log on to the c.i.e.
b) Navigate to menu H7.
c) Write the zone number (for example 001) and press
d) Press
to start the test. Indicated by "√" and a beep.
Set in test mode
Zone 001
-- End test mode ---------------------------------------------
---
Zone 001
END TEST MODE
e) Use the soft key
- Set in test mode
- End test mode list
f) After the testing, select a zone in the "End test mode" list and press
The test mode must be ended for all zones.
to toggle between:
.
.
114