FAULT: Restart control unit nn,
code xx, address yyyyyyyyyy
A restart has occurred in control unit no. nn. SSD and S/W download will automatically be followed by a restart. Also, you can
manually do a restart. Regarding the restart codes 00, 03, 13, 14, 25, 50 & 53, see chapter
The following restart codes are because of some external disturbance and are not normal, i.e. call for service personnel / engi-
neer:
xx=01: Watchdog Reset.
xx=02: Accidental jump to reset vector.
xx=04-12: Unexpected interrupt.
xx=13: S/W monitoring fault
yy...y = memory address (before restart). Write down the address and inform the service personnel/engineer.
FAULT: Second network, CU xx <-> CU xx,
detected by CU xx
Control unit xx has detected a network fault on the secondary network between the two control units listed.
Check cables, connections, etc. This could also mean a faulty 5040 board in either of the two control units listed.
FAULT: Sensor zone: xxx address: xx
technical number xxxxxx
The analog smoke, heat or multi detector is faulty. The detector's built-in self-verification function has reported a fault. The detec-
tor has to be replaced.
FAULT: Short circ. tech addr nnn <-> nnn, [sub-loop x], loop x, CU xx
Tech addr nnn <-> nnn describes between which Short Circuit Isolators the short-circuit is located.
nnn = Technical address for short circuit isolator. A & B is the built-in isolator in the EBL512 G3 c.i.e.
A-direction and B-direction respectively.
Each 10
minute a check is performed if all short-circuits are corrected (repaired). If so, the communication
th
automatically returns to communicate in one direction only.
The fault has to be acknowledged, i.e. and it can last up to 10 minutes after the acknowledgement before the
communication returns to communicate in one direction only.
This fault might be incorrectly shown if the SA-SB cables are mixed. If no short circuit can be found, run
"check loop" from EBLWin to get correct information.