EBL512 G3 V. 3.0.X - FIRE ALARM SOLUTIONS OPERATING INSTRUCTIONS
IN CASE OF A PRE-WARNING, THE FOLLOWING HAPPENS:
The buzzer in the c.i.e. sounds 0.8 sec. each 5th sec. (0.8 / 5 sec.).
Outputs programmed for pre-warning are activated.
In the c.i.e. display, a presentation number (zone/address) is shown (for the first pre-warning).
In the c.i.e. display, a user definable text message (= the alarm text for fire alarm) is shown (if programmed).
Example; pre-warning zone 123, address 45 (within zone 123):
Pre-warning
123-45
Zone
User definable alarm text for 123-45
Menu
"SMOKE" after the presentation number is automatically added depending on the type of alarm point (SMOKE, HEAT, MULTI or
MCP).
If more than one pre-warning is activated, the LEDs "Alarms queued" are blinking and the pre-warnings will be automatically scrolled
(each five seconds).
Pre-warnings are automatically reset, see chapter
Address
SMOKE
19. ALARM RESET
on page 50.