EBL512 G3 V. 3.0.X - FIRE ALARM SOLUTIONS OPERATING INSTRUCTIONS

9. TECHNICAL NUMBER

The technical number, NNNNNN, is used when programming all units connected to the COM loops. Technical number is also used
to identify which unit has generated a fault.
NN
N
00-29
0-3
The control unit address
COM loop number
(number), Don't have to be
in sequence. The connec-
tions to the network don't
have to be in sequence.
The address is set with a
PC SW; in case of a 5040
network with EBLWin and
in case of a TLON network
with TLON Manager
Totally 1012 COM loop (technical) addresses can be used for one control unit, of which up to 512 address-
es can be used for alarm points.
A brand new detector is factory set to COM loop (technical) address 000. Connected on the COM loop, the detector LEDs will start
blinking every second, indicating that an address (001 - 253) has to be set before the detector will work.
Since (technical) address 000 cannot be used, the total number of addresses is 4 x 253 = 1012
NNN
001-253
The technical address on
the COM loop.
The addresses don't have
to be in sequence.
The connections on the
COM loop don't have to be
in sequence.
The address for each unit is
set during auto addressing
or with the programming
tool 4414E.