EBL512 G3 V. 3.0.X - FIRE ALARM SOLUTIONS OPERATING INSTRUCTIONS

28.4. ALARM DEVICES (H2/B4)

All outputs of type "Alarm device" and "Alarm device for evacuation" can be collectively disabled.
Disabled output will stay in (or return to) the normal condition for the output respectively.
Disabled outputs are listed in menu H4/U1 from which it is also possible to get a print-out.
DISABLE:
a) Log on to the c.i.e.
b) Navigate to menu B4.
c) By default "All alarm devices" is selected.
d) Press
to disable.
RE-ENABLE:
e) Use the
to toggle between:
- Disable
- Re-enable list.
f) Select "Re-enable list".
g) Press
to re-enable.

28.5. ROUTING EQUIPMENT (H2/B5)

Disabled outputs are listed in menu H4/U1 from which it is possible to get a print-out. Outputs for routing equipment (fire brigade
tx and fault tx) can be disabled and re-enabled via this menu. Can be useful during an installation and test period, when only local
alarms are required.
Disabled output for routing equipment is indicated by LEDs Fault / Disablements "General disablements" and "Fire brigade tx".
Disabled output will stay disabled until re-enabled again via this menu.
DISABLE:
a) Log on to the c.i.e.
b) Navigate to menu B5.
c) Press
to toggle between:
- Fire (by default Fire is selected)
- Fault
d) Press
to disable.
RE-ENABLE:
e) Use the
to toggle between:
- Disable
- Re-enable list
f) Select "Re-enable list".
g) Press
to select the type that shall be re-enabled.
h) Press
to re-enable.