EBL512 G3 V. 3.0.X - FIRE ALARM SOLUTIONS OPERATING INSTRUCTIONS

34.7. SYNCHRONIZE THE CONTROL UNITS (H8/S7)

After any control unit restart, synchronization will start automatically. Synchronization can also be started via EBLWin and via this
menu (H8/S7). The control units must be synchronized when the following fault message is shown:
FAULT: Control unit xx has wrong information.
↻ = Synchronization in progress for the control unit (CU) respectively.
During the synchronization there will be information displayed for all control units in the system.
√ = Synchronization completed successfully for the control unit (CU) respectively.
<Blank> = Synchronization failed for the control unit (CU) respectively.
a) Log on to the c.i.e.
b) Navigate to menu S7.
c) Write control unit number and press
Start synchronization?
d) Press
to start the synchronization. During the synchronization the progress symbol for each control unit is shown. In the
example
CU00 ↻
CU03 ↻
Synchronization in progress...
CU01 ↻
CU04 ↻
CU02 ↻
CU05 ↻
Synchronization completed
yyyy-mm-dd hh:mm
CU00 √
CU03 √
CU01 √
CU04 √
CU02 √
CU05 √
Date and time for the latest completed synchronization will show. The symbol "√" means that the synchronization succeeded. If the
symbol "√" is missing the synchronization has failed
Start synchronization?
e) Press ESC to leave this dialog.
f) Press ESC to leave this menu.
to select "Yes.
No
Yes
CU06 ↻
CU07 ↻
CU08 ↻
CU06 √
CU07 √
CU08 √
No
Yes