Sensor Values (H4/U4) - Panasonic EBL512 G3 Operating Instructions Manual

Hide thumbs Also See for EBL512 G3:
Table of Contents

Advertisement

30.4. SENSOR VALUES (H4/U4)

Information on heat, smoke or multi detector sensor values.
a) Log on to the c.i.e.
b) Navigate to menu U4.
c) Write the technical number for a specific sensor or press
If there are no sensors (analog detectors) when
d) Scroll in the list with
e) To exit the menu press ESC.
For an Analog multi detector 4300 / 4400 in NORMAL mode:
Sensor: 001-01 (technical address 000001)
Momentary: XX.X%/m
Perf factor: X.XX%/m
Algorithm: X-XX
Momentary: XX°C
Algorithm: XX
For an Analog heat detector 3308 / 3309 in NORMAL mode:
Sensor: 001-03 (technical address 000002)
Momentary: XX°C
Algorithm: XX
For an Analog multi detector 4400 in Advanced mode:
Sensor: 001-01 (technical address 000001)
Momentary: XX.X%/m
Perf factor: X.XX%/m
Algorithm: Xxxxxx
Momentary: XX°C
For an Analog multi detector with CO 4402 in NORMAL mode:
Sensor: 001-01 (technical address 000001)
Momentary: XX.X%/m
Perf factor: X.XX%/m
No. of months left: XX
Momentary: XX°C
Momentary: XXppm
For an Analog multi detector with isolator 4400I in Advanced mode:
Sensor: 001-01 (technical address 000001)
Momentary: XX.X%/m
Perf factor: X.XX%/m
Algorithm: Normal
Momentary: XX°C
Install date: XXXX-XX-XX
.
Weekly: XX.X%/m
Min: XX.X%/m
Max: XX.X%/m
Min: XX°C
Max: XX°C
Min: XX°C
Max: XX°C
Weekly: XX.X%/m
Min: XX.X%/m
Max: XX.X%/m
Min: XX°C
Max: XX°C
Weekly: XX.X%/m
Min: XX.X%/m
Max: XX.X%/m
Min/Max: XX/XX°C
Weekly: XXppm
Weekly: XX.X%/m
Min: XX.X%/m
Max: XX.X%/m
Min: XX°C
Max: XX°C
to start as from sensor 000001.
is pressed, the list view will not open.