EBL512 G3 V. 3.0.X - FIRE ALARM SOLUTIONS OPERATING INSTRUCTIONS
TLON NETWORK INSTALLATION (SINGLE)
a) Create a project in the PC program TLON Manager.
b) Connect a PC to the modular connector "J10" (Network no. 0) in a control unit. Open the project in TLON Manager and install
(download) the project.
For more information see separate Technical description TLON Manager Kit MEW01983.
TLON NETWORK INSTALLATION (REDUNDANT)
In a redundant network two Projects have to be created and installed. The Projects have to be identical but with different Project
names.
One project has to be installed for Network no. 0 and one has to be installed for Network no. 1.
If a redundant TLON Network shall be used, a PC is connected to the modular connector "J11" (Network no. 1) and the same proce-
dure as for Network no. 0 is done for Network no. 1.
After the TLON Network installation (download) it is highly recommended to restart the control units.

23.3. ADD A CONTROL UNIT INTO A NETWORK

When adding a new control unit to a "running" installation you must have the same software (S/W) version in all control units. Often
the new control unit has a newer version than the existing control units.
Normally the latest version is the best to use. That means the control units in the "running" installation must be upgraded. As an
alternative, it is possible to download an earlier S/W version in the new control unit.
When the control unit is equipped with a network board 5040, the lowest S/W version is 3.0.0.
Both alternatives are described in Planning Instructions for this system.
5040 NETWORK:
Open the SSD for the current system via EBLWin. Add one control unit (and the units connected to it) and set the control unit ID
according to
17.3.8 SET CONTROL UNIT ID
Download the new SSD according to Planning Instructions for this system.
Do not forget to add the new control unit in the network ring, see section 16.3.7 SYSTEM PROPERTIES,
PAGE 4 in Planning Instructions for this system.
TLON NETWORK:
a) Open the current project in TLON Manager
b) Add one control unit and install (download) it according to Technical description MEW01983.
Also see section
TLON NETWORK INSTALLATION (SINGLE)
c) Open the SSD for the current system via EBLWin. Add one control unit (and the units connected to it) and download the new
SSD according to Planning Instructions for this system.
in Planning Instructions.