Panasonic EBL512 G3 Operating Instructions Manual page 62

Hide thumbs Also See for EBL512 G3:
Table of Contents

Advertisement

FAULT: Fan, technical number xxxxxx
The LED "Fault" is lit on a fan control module connected to control unit xx. Fan no. xx has been activated but the corresponding
I/O unit 4461 input has not been activated within the programmed time. Check the fan and the cables / connections.
FAULT: Fault warning routing equipment,
control unit xx
The fault is to be found in the Fault warning routing equipment. A routing equipment fault output is connected to a programmable
supervised input in the EBL512 G3 system, in control unit no. xx.
Check the input connections as well. (Normally used for German routing equipment connected to an expansion board 4583).
FAULT: Fire brigade panel xx,
control unit xx
5054 (Ext. Fire Brigade Panel - FBP)
The ext. FBP xx, connected to control unit no. xx, is programmed as another type in the SSD or a fault in the unit.
FAULT: Fire brigade panel xx, channel x, CU xx
5054 (Ext. Fire Brigade Panel - FBP)
The ext. FBP xx, connected to channel x, control unit no. xx, is programmed as another type in the SSD or a fault in the unit.
FAULT: Fuse output x,
technical number xxxxxx
Blown fuse 0, 1 or 2 on the 4464 board or in power supply 4466.
Replace the fuse.
FAULT: Fuse, supervised output x (auto-resettable), CU xx
x = 0-3, xx = 00-29.
The auto-resettable fuse PTC7 (for output 0), PTC8 (for output 1), PTC5 (for output 2) or PTC6 (for output 3) (max 500mA) has
been activated. Check for overload on the equipment connected to the output.
To reset the PTC, disconnect the connected equipment and wait 5 min to let the PTC cool down before re-connecting the equip-
ment.
FAULT: General control panel xx, CU xx
5054 (General control panel - GCP)
The GCP xx, connected to control unit no. xx, is programmed as another type in the SSD or a fault
in the unit.
62

Advertisement

Table of Contents
loading

Table of Contents