After Restart - Panasonic EBL512 G3 Operating Instructions Manual

Hide thumbs Also See for EBL512 G3:
Table of Contents

Advertisement

EBL512 G3 V. 3.0.X - FIRE ALARM SOLUTIONS OPERATING INSTRUCTIONS

34.5.1. AFTER RESTART

After a restart, see chapter
off / Power on restart and 03 / 53 after a countdown restart. Address 0. This fault must be acknowledged, see chapter
on page 113.
ACKNOWLEDGE (H6)
FAULT: Restart control unit 00, code 50,
address 0
2019-12-03
09:09
FAULT: Restart control unit 00, code 00,
Address 0
2019-11-03
09:08
Menu
Code 50 and 53 respectively will only appear if the control unit has an MMI board.
Before the very first safe shut down the Flash ROM is empty. Then every time safe shut down is performed
the valid data will be saved in the Flash ROM, i.e. any old data will be overwritten. When the c.i.e. is pow-
ered up, the data stored in the Flash ROM will be used.
If safe shut down is not performed just before you power off a control unit, then by power on, the Flash
ROM might be empty which means the default settings will be used. Or the stored data might be old and
not valid.
on page 82, there will always be two restart faults. The code will be 00 / 50 after Power
25. RESTART
/Serviced
/Serviced
121