18.1.2. FIRE ALARM

The system can handle up to 15360 fire alarms but only 512 fire alarms can be shown in the c.i.e. display. If more than 512 fire
alarms are activated, no more fire alarms will be shown until one or more of the first 512 fire alarms are reset.
Normally all fire alarms will be presented in all control units (default) but it is possible to have Selective alarm presentation, i.e. only
fire alarms from selected control units will be presented in the control unit respectively. Set in EBLWin for each control unit.
See also section
5.4. INFORMATION PRIORITY ORDER
THE FOLLOWING HAPPENS IN CASE OF A FIRE ALARM:
(In accordance with the EN54-2 standard.)
The buzzer in the c.i.e. sounds 0.4 sec. each 0.4th sec. (0.4 / 0.4 sec.).
LEDs "Fire" (L1) are blinking (0.4 / 0.4 sec.).
Output for routing equipment (Fire brigade tx) is activated. In case of Selective alarm presentation only for the selected alarms.
Outputs for fire alarm are activated. Outputs programmed for General fire alarm and outputs programmed for the activated fire
alarm(s).
In the c.i.e. display, a presentation number (zone/address) is shown (for the first fire alarm).
In the c.i.e. display, a user definable text message (alarm text) is shown (if programmed).
In the c.i.e. display, is also some additional information presented.
ONE ALARM POINT ACTIVATING FIRE ALARM.
Example; fire alarm zone 002, address 03 (within zone 002):
Fire alarm: 002-03
Pre-warning
002-03
Zone
User definable alarm text for 002-03
Menu
After the presentation number is automatically added SMOKE, HEAT, MULTI or MCP depending on type of alarm source, for more
information see section
18.2. ALARM SOURCE
on page 18.
Alarm number 1 (of 1)
Address
SMOKE
1 zone in alarm
on page 49.
38