18.1.5. KEY CABINET ALARM

The fire brigade uses a key cabinet to store a key to the building.
One programmable input per c.i.e. can be used to connect a key cabinet.
A key cabinet alarm is like a normal fire alarm, i.e. outputs with trigger condition "General fire alarm" will be activated as well as
outputs with trigger condition "Activated key cabinet"
KEY CABINET OPENED BEFORE A FIRE ALARM
If the key cabinet is opened without a fire alarm, for example if somebody illegally breaks into the key cabinet, a key cabinet alarm
will be activated. An example, XX = Control Unit number (00-29):
Fire alarm: 000-00
Alarm from key cabinet control unit XX
Menu
When printer is available the Key cabinet alarm will be printed like for a normal fire alarm (see above).
Key cabinet alarm is reset like a normal fire alarm, see section
This alarm will also generate a fault message, see section
"General fault" and the "Fault tx" output(s) will be activated.
Alarm number 1 (of 1)
19.2. FIRE ALARM RESET
19.6. KEY CABINET ALARM RESET
on page 50.