Panasonic EBL512 G3 Operating Instructions Manual page 68

Hide thumbs Also See for EBL512 G3:
Table of Contents

Advertisement

FAULT: No reply expansion board x loop x
control unit xx
This is valid for the I/O Matrix board (4582) no. x, connected on COM loop x in the control unit no. xx.
Check the board's address, i.e. the I/O Matrix board no. (Jumpers JP1, JP2 and JP3 on the board).
Check if the board is disconnected from the loop.
FAULT: No reply, alert annunciation unit xx,
channel x, control unit xx
FAULT: No reply, external presentation unit xx
Channel x, control unit xx
FAULT: No reply, fire brigade panel xx,
channel x, control unit xx
FAULT: No reply, General Control Panel xx,
channel x, CU xx
Alert Annunciation Unit
External Presentation Unit
External Fire Brigade Panel
General Control Panel
The contact with the unit is interrupted. Check the cable, all connections, etc. Is correct / complete SSD downloaded (via
EBLWin)? Check the address and SW mode settings.
FAULT: No reply Loop unit xxxxxx
The unit (e.g. a customized unit), cannot be found by the control unit.
Check the unit's COM loop address (with the programming tool 3314 / 4414).
Check the downloaded site specific data (SSD).
The unit might be faulty.
The unit might be removed from the COM loop.
There might be a double break or short-circuit on the COM loop.
FAULT: No reply zone: xxx address: xx
technical number xxxxxx
The unit cannot be found by the control unit.
Check the unit's COM loop address (with the programming tool 3314 / 4414).
Check the downloaded site specific data (SSD).
The unit might be faulty.
The detector might be removed from its base.
There might be a double break or short-circuit on the COM loop.
Valid for a wireless smoke detector 4611or wireless manual call point 4614:
Battery voltage < 2.3 V or the Base station (4620) does not receive any detector data.
68